Energetech
Solar
User Manual
Specs Sheet
Specifications
Package
No.
Item
General Parameter
Remark
1
Combination
method
16S2P
2
Rated Capacity
200Ah
Standard discharge after Standard charge(package)
3
Factory Voltage
51.2V
Mean Operation Voltage
4
Voltage at end of Discharge
46V
Discharge Cut-off Voltage
5
Charging Voltage
56V
Charge Cut-off Voltage
6
Internal
Impedance
=60mO
Internal resistance measured at AC 1KHZ after 50% chargeThe
measure must uses the new
batteries that within one week after shipment and cycles less than 5 times
7
Standard charge
Constant Current 50A Constant Voltage see No.5 0.02CA cut-off
Charge time : Approx 2.5 h
8
Maximum
Continuous
Charge Current
100A
9
Standard
discharge
Constant current:50A end voltage see NO.4
10
Discharge
Current
150A
100A when T=10ºC
50A when 0ºC>T=-20ºC
11
Operation
Temperature
Range
Charge: 0~45?
60±25%R.H.
Bare Cell
Discharge: -20~55?
12
Storage
Less than 12 months :
-10~35?
at the shipment state
less than 3 months:
-10~45?
Less than 7 day :
-20~65?
13
Dimensions
720*550*200mm
Include Bracket
14
Weight
Approx :102.5 kg
(N.W)
104.5kg (G.W)
15
BMS Port
CANBUS/RS485
16
BMS Support
16PCS Parallel
160KWH at max
Warning: Do NOT remove power when the inverter is turned on.