50KWh 48 Volt Module
Energy Storage System
These systems can be paralleled up to 14 systems.
50KWh System - $24,700*
100KWh System - $49,400*
150KWh System - $74,100*
200KWh System - $98,800*
250KWh System - $123,500*
*Plus Shipping - FOB China
Systems Over 250KWh – Contact us for pricing
Battery Cell Specifications:
Nominal Capacity: 100Ah
Nominal Voltage: 3.2V
Internal Impedance: <0.4
milliohms
Weight: 5.0 Lbs. (2.25Kg)
Energy Density: 142 Wh/Kg
RT Cycle Life: 5000 cycles
Low Temperature Discharge Cap
Retention: >90%
Self-discharge Rate: <3%
per month
Standard Charge Current: 50A
Max Continuous Charge Current:
200A
Limited Charge Voltage: 3.65V
Standard Discharge Current:
100A
Max Continuous Discharge
Current: 200A
Discharge Cut-off Voltage:
2.5V
Operating Charge Temperature:
32~131F (0~55C)
Operating Discharge
Temperature: -4~140F (-20~60C)
Storage Temperature: -4~104F
(-20~40C)
Storage Humidity: 15%~90% RH
Storage State of Charge (SOC):
30%~50%
Delivery Capacity (SOC): 30%
Battery Module
Specifications:
Nominal Voltage: 48V
Actual Voltage: 51.2V
Nominal Capacity: 100Ah
Configuration: 1P16S
Weight: <132 Lbs.
(<60Kg)
Max Continuous Discharge
Current: 200A
Max Continuous Charge Current:
100A
Peak Discharge Current: 300A
(1 min); 350A (10s)
Peak Charge Current: 200A
Charge Working Temperature:
32F~131F (0C~55C)
Discharge Temperature:
-4F~140F (-20C~60C)
Insulation Requirement: More
than 500 milliohms
Heating Method: No
Dimensions: 24.1 * 19.7 * 6.5
in. (612 * 500 * 165.5mm)
Battery
Cluster Specifications:
Nominal Voltage (50% SOC): 48V
Actual Voltage (50% SOC):
51.2V
Nominal Capacity: 1000Ah
Cluster Configuration: 16S10P
Cluster Total Energy: 51.2KWh
Cluster Available Energy:
47.1KWh
Voltage Range: 40V~58.4V
Max Pulse Discharge Current:
3000A (1 min); 3500A (10s)
Max Continuous Discharge
Current: 2000A
Max Pulse Charge Current (10s):
1500A
Max Continuous Charge Current:
1000A
Max SOC Operating Window: 5%
SOC~97% SOC
Life Cycles: >3500 cycles
Max CP/CC Charge Voltage:
56.8V
Min CP/CC Discharge Voltage:
45.87V
1.15 Month, (25C), 50% SOC
Self-discharge: 3%
Insulation Resistance Value:
More than 30 milliohms
IP Grade: IP21
Dimensions: 27.6 x 33.9 x 86.6
in. (700mm x 860mm x 2200mm)
Weight: 1,764 Lbs. (800Kg)
The battery cabinet is mainly
installed with a battery box and a BMS main management system, supporting wires
and cables, and high and low voltage electrical protection components. The
cabinet adopts a grouped and layered design, which has a beautiful appearance.
The cabinet adopts maintenance-free technology and modular assembly structure
to ensure that the cabinet structure has good mechanical strength, and the
overall structure can meet the reliability
and safety of the entire system to the greatest extent. The battery system is composed
of 10 layers and 1 column.
Battery Management System
(BMS) Basic Functions
The BMS mainly includes
battery status monitoring operation control, event record storage function,
insulation monitoring, dynamic balance management, protection alarm,
communication and other functions to ensure normal, stable and reliable system
operation.
BMS Specifications
BMS Mode: Main controller;
Sub-controller
BMS Power Supply: Battery
power (Take power directly from the general positive and negative terminals of
the battery.)
Cell Voltage Acquisition: 16S
qty
Temp Acquisition: 80 points (8
for each module)
Current acquisition: Current
diverter
SOC Estimation Accuracy:
<5%
External Communication
Interfaces and Channels: 2 CAN, 1 internal CAN, 1 debug CAN
Termination Resistor Location:
120 milliohms resistor at the battery box 10 harness end
Reverse Power Protection
Balancing Requirement: Passive
Balancing Current: <100mA
Display Screen: 7.0 inch, 48V
power supply, CAN communication
Voltage Control Information
(module): Channel 1 charge control, 1 discharge control, 1 current limit
control