24kW Inverter/Charge Controller
48V DC Input
240V 50Hz or 60Hz Output
40A Battery Charger
Pure Sine Wave
Three Phase
Works With Lithium or Lead Acid Batteries
25.6L * 20.2W * 31.6H in
650 * 513 * 803 mm
386 Lbs. / 175 Kg
View the Inverter Manual Here with mechanical drawings, features, and performance information!
Pricing Options
$6,690 – Total cost with ocean freight shipping to nearest International seaport in the Continental USA – Allow for 8-10 week delivery
Call for pricing above 5 each at (801) 566-5678
Features:
Smart LED Remote Control
Battery Temperature Sensor (BTS)
Automatic Generator Start (AGS)
Designed for Harsh Environment Operation
DC Start & Automatic Self-Diagnostic Function
Easy to Install & Easy to Operate & Easy to Solve
Low DC Voltage Supports Home & Office Appliances
High Energy Charging Function, Selectable From 0%-100%
High Efficiency Design & “Power Saving Mode” to Conserve Energy
Battery Priority Mode, Designates the Inverter-Preferred UPS Configuration
26/52Vdc Battery Recover Point, Dedicated for Renewable Energy Systems
8 pre-Set Battery Type Selector Plus De-sulphation for Totally Flat Batteries
4-step Intelligent Battery Charging, PFC (Power Factor Correction) for Charger
Independently controlled three-phase output voltages & Load,100% Unbalanced load
0ms Transfer Time from Battery to Utility ;8ms Typical Transfer Time from Utility to Battery
15s Delay Before Transfer when AC Recover, Protection for Load when Used with Generator
Output Specifications:
Continuous Output Power: 24,000 Watts
Surge Rating: 72,000 Watts (20 Seconds)
Capable of Starting Electric Motor: 24HP
Acceptable Unbalanced Load: 100%
Output Waveform: Pure Sine Wave/Same as input (Bypass Mode)
Output Phase Voltage: 240Vac
Nominal Efficiency: 89% (Peak)
Line Mode Efficiency: >95%
Power Factor: 0.9-1.0
Connection Mode: 3-phase 4-wire system + Ground
Output Voltage Rating: 3AC/N 400V or 208V
Output Voltage Regulation: 10% RMS
Output Frequency: 50 or 60 Hz +/- 0.3Hz
Short Circuit Protection: Yes, Current Limit Function (Fault after 60ms)
Typical Transfer Time: 6-8ms (10ms Max)
THD: <3% (Linear Load)
Input Specifications:
Nominal Input Voltage: 48VDC
Minimum Start Voltage: 42VDC / 44VDC
Low Battery Alarm: 42VDC / 44VDC
Low Battery Trip: 40V / 42V
High Voltage Alarm & Fault: 64VDC
High DC Input Recovery: 62VDC
Low Battery Voltage Recover: 52VDC
Idle Consumption Search Mode: <100 Watts (when Power Saver on)
Charger Specifications:
Output voltage: Same as input
Charger Breaker Rating (240VAC): 40A
Max Charge Rate: 240A
Power Factor: 0.97 MAX
Over Charge Protection Shutdown: 15.7 for 12VDC (*2 for 24VDC, *4 for 48VDC)
Battery Type: Float VDC